CITY OF BANGOR WASTEWATER TREATMENT PLANT
LOCAL LIMITS
THE FOLLOWING ARE THE LOCAL LIMITS AS APPLIED TO THE
DISCHARGE OF WASTEWATER TO THE CITY OF
BANGOR WASTEWATER TREATMENT PLANT AND SEWER SYSTEM. FOR INDUSTRIES
SUBJECT TO FEDERAL CATEGORICAL PRETREATMENT STANDARDS, DISCHARGE LIMITS SHALL
BE AS PER THE CODE
OF FEDERAL REGULATIONS TITLE 40, HOWEVER, IN ALL CASES THE
LOWEST APPLICABLE LIMIT SHALL BE THE
POINT OF ENFORCEMENT.
|
POLLUTANT CONCENTRATION
LIMIT (mg/l) |
||
|
Arsenic.............................................. ...24 |
||
|
Cadmium.............................................. |
|
.75 |
|
Chromium........................................... . |
|
5.00 |
|
Copper................................................ |
|
27.40 |
|
Cyanide.............................................. . |
|
6.12 |
|
Lead.................................................. .. |
|
3.87 |
|
Nickel................................................. |
|
14.51 |
|
Mercury.............................................. |
|
.20 |
|
Selenium.............................................. |
|
1.00 |
|
Silver.................................................. . |
|
2.16 |
|
Zinc..................................................... |
|
13.57 |
|
Total Oil & Grease............................... |
|
200.00 |
|
pH..................................................... . |
5 |
– 12 su |
TOTAL TOXIC ORGANICS ARE
MONITORED AS PER FUME TOXICITY SCREENING LEVEL
CALCULATIONS BASED ON “HENRY’S LAW”.
THE CITY OF BANGOR THROUGH CHAPTER 252 OF THE CITY
CODES AND ORDINANCES RESERVES THE RIGHT TO
LEVY SURCHARGES TO USERS OF THE SEWER SYSTEM AS DEEMED NECESSARY BY THE
SUPERINTENDENT.
SURCHARGES MAY BE LEVIED WHEN
CONCENTRATION OF THE FOLLOWING POLLUTANT(S)
EXCEED 140 mg/l:
1). Total
Oil & Grease
SURCHARGES MAY BE LEVIED WHEN
CONCENTRATION OF THE FOLLOWING POLLUTANT(S)
EXCEED 350 mg/l:
1).
Biochemical
Oxygen Demand
2).
Total
Suspended Solids